Skip to main content
All incident reports
Incident report

Unpatched critical flaw in Danfoss refrigeration controllers, CISA warns

CISA has published an advisory on a critical, unpatched buffer overflow in Danfoss AK-SM 8xxA refrigeration controllers that an unauthenticated attacker could use to restart the device or run code with web server privileges. It follows attacks on European supermarket cooling systems, though no source says those attacks used this flaw.

· First published

The short version

  • The flaw. CVE-2026-129713 is a stack-based buffer overflow in an unauthenticated web handler of the Danfoss AK-SM 8xxA Series, scored 9.8 under CVSS 3.1. CISA says crafted HTTP or HTTPS requests can corrupt memory, restart the web server and, hypothetically, let an attacker run code with web server privileges.
  • No patch yet. Versions up to and including 5.4.0 are affected. Danfoss published an advisory on 20 November saying a fix will arrive in version 5.5.x, which will also remove the option to disable Strict Mode; BleepingComputer reported on 25 November that no patch was yet available.
  • Attacks in Europe. BleepingComputer reports that Danfoss controllers have been compromised at food retailers: French supermarkets in October, and at least 115 stores in seven countries on 2 November, where cooling was shut down or settings changed remotely.
  • Link not established. CISA says no known public exploitation of this specific vulnerability has been reported to it, and BleepingComputer does not state that the recent attacks used CVE-2026-129713. The sources do not prove the campaign and the advisory describe the same mechanism.

Timeline

DateEvent
11-12 OctFrench supermarkets and food retailers suffer losses after attackers change defrost settings on Danfoss AK-SM/AK-SC and Copeland/Dixell XWEB refrigeration controllers.
2 NovAt least 115 supermarket stores in Belgium, the Netherlands, Sweden, Luxembourg, Ireland, Romania and Estonia have refrigeration shut down or settings changed remotely.
2 NovCold-storage settings are altered at three facilities of a refrigeration supplier to the French national blood service.
20 NovDanfoss publishes a security advisory saying CVE-2026-129713 will be addressed in software version 5.5.x.
24 NovCISA publishes its advisory on the vulnerability.
25 NovBleepingComputer reports the CISA warning and the earlier attacks on refrigeration systems.

The vulnerability

CISA issued an industrial control systems advisory on 24 November for CVE-2026-129713, a stack-based buffer overflow in the Danfoss AK-SM 8xxA Series. CISA says the fault is in an unauthenticated CGI handler, the component that processes web requests, so an attacker can send crafted HTTP or HTTPS POST requests without logging in. That causes memory corruption and a web server restart; CISA describes arbitrary code execution with web server privileges as hypothetical. The agency scores it 9.8 under CVSS 3.1.

Versions up to and including 5.4.0 are listed as affected. According to BleepingComputer, Danfoss published its own advisory on 20 November saying the issue will be fixed in version 5.5.x, and that the release will also remove the ability for customers to turn off Strict Mode. No patch was available when BleepingComputer reported on 25 November. Carlo Meijer of Midnight Blue reported the flaw to CISA.

Who is affected

The controllers are central units for supermarkets and convenience stores, managing refrigerated display cases and compressor racks, logging temperatures and alerting when changes occur. Depending on the model — the line includes the 820A, 850A and 880A — they also control store lighting and HVAC. CISA says they are deployed worldwide but gives no count.

BleepingComputer reports that Danfoss controllers have been compromised in recent attacks on food retailers in Europe. Between 11 and 12 October, French supermarkets suffered losses after attackers changed defrost settings on Danfoss AK-SM/AK-SC and Copeland/Dixell XWEB controllers; the article says the attacks were attributed to Iran's IRGC-linked Shahid Kaveh unit, without naming who made that attribution. On 2 November, at least 115 stores in seven countries had refrigeration shut down or settings changed.

Also on 2 November, a refrigeration supplier to the French national blood service was targeted and cold-storage settings were altered at three facilities, with the attackers suspected of belonging to the same campaign. Supplier Sabcobel said the vulnerability used was the same one seen in the October attacks in France, which BleepingComputer treats as a sign that Danfoss systems were involved again.

What is not established

CISA states that no known public exploitation specifically targeting this vulnerability has been reported to it. BleepingComputer's account of the recent compromises does not say those attacks used CVE-2026-129713, and Sabcobel's reference to the same vulnerability as in October is not tied to a CVE identifier in the article. The sources therefore do not establish that the campaign and the advisory describe the same mechanism.

The advisory and the attack reporting also differ in scope. CISA's document covers one product line, the AK-SM 8xxA Series, while the October incidents described by BleepingComputer involved Danfoss AK-SM/AK-SC controllers and Copeland/Dixell XWEB equipment as well. Neither source says how many devices are reachable from the internet or how many stores run the affected versions.

What is not known yet

  • Who carried out the October and November attacks, and whether those attacks exploited CVE-2026-129713.
  • How many AK-SM 8xxA controllers are deployed, and how many are exposed to the internet.
  • Whether any attacker achieved code execution on a controller, rather than only changing settings or forcing restarts.
  • When version 5.5.x will be released.
  • Whether Strict Mode had been disabled on any of the controllers involved in the attacks.

What to do

If you run Danfoss AK-SM 8xxA controllers

  1. Remove direct internet access to the controllers and place them behind a firewall, separated from business networks.
  2. Where remote access is needed, require an up-to-date VPN rather than exposing the device itself.
  3. Apply software version 5.5.x when Danfoss releases it, and leave Strict Mode enabled in the meantime.

If a supplier manages your refrigeration

  1. Ask whether AK-SM 8xxA controllers are in use at your sites and what network controls sit in front of them.
  2. Confirm that temperature logging and change alerts are monitored, so a remote settings change is noticed quickly.

For everyone else

  1. Inventory building and refrigeration controls that answer on the public internet and close that exposure before a patch exists.

Update log

  • First published.