Skip to main content
All incident reports
Incident report

Cyberattack defrosts refrigeration at Coopérative U, Intermarché and other European chains

Attackers remotely took over refrigeration controllers at supermarket chains in France and several other European countries overnight on 11 October and triggered defrost cycles, spoiling fresh food. Retailers and French media say the units were Danfoss controllers running older software; Danfoss has not publicly confirmed it was the target, and no source says how the attackers got in.

· First published

The short version

  • The attack. Attackers remotely reached refrigeration controllers at supermarket chains in France and elsewhere in Europe overnight on 11 October and triggered defrost cycles, spoiling fresh food. Staff found the damage when they opened the units in the morning.
  • Scale and cost. BFMTV reported about 300 Intermarché and Netto stores and fewer than 100 Coopérative U stores affected; other reports gave 250 to 350 stores, or more than 300 locations in France. SecurityWeek reported effects in six other European countries and losses estimated in the millions of euros.
  • The equipment. Reports say the affected units were Danfoss controllers running older software. Danfoss has not publicly confirmed that its systems were the target. No source establishes how the attackers reached the devices, or whether flaws Claroty disclosed in the AK-SM 800A platform were used.
  • Official response. Coopérative U's chief executive confirmed the attack on his chain, ANSSI said it was mobilised, the Paris prosecutor's office opened an investigation and an EU commissioner condemned the attack.

Timeline

DateEvent
May 2025CISA warns of CVE-2025-41450, a high-severity authentication bypass in the Danfoss AK-SM 8xxA platform used to manage refrigeration and HVAC systems in food retail, BleepingComputer reports.
11 OctAttackers set refrigeration controllers at supermarket chains to defrost overnight; staff find spoiled fresh food in the morning.
11 OctDominique Schelcher, chief executive of Coopérative U, confirms that the attack affected the refrigeration systems of several stores in the chain.
12 OctThe Paris prosecutor's office tells AFP it has opened an investigation into the attacks, to identify victims and establish the link with reported food losses.

How the attack unfolded

Overnight on 11 October, attackers reached refrigeration controllers at supermarket chains and set them to defrost, according to the retailers and French media. Staff arriving in the morning found fresh food spoiled. BleepingComputer reported that the controllers ran older versions of Danfoss control software and that the attackers used a built-in automatic defrost function. SecurityWeek said temperatures were reportedly raised to 50°C and that in some cases they climbed for six hours before staff noticed.

Security researcher Lukasz Olejnik described the effect: "Someone remotely took over refrigeration controllers and made them defrost." How the attackers reached the devices is not established. BleepingComputer said no information was available on how the controllers were compromised. SecurityWeek said the attackers exploited a vulnerability in the controllers, but also that it was unclear whether flaws Claroty had disclosed in the Danfoss AK-SM 800A platform, which allowed authentication bypass and remote code execution, were the ones used.

Who is affected

The chains named across the reports include Intermarché and Netto, both owned by Groupement Mousquetaires, Coopérative U, Carrefour Market, Monoprix, Leclerc, Super U and Auchan. Estimates vary: BFMTV reported about 300 Intermarché and Netto stores and fewer than 100 Coopérative U stores, BleepingComputer reported between 250 and 350 stores, and SecurityWeek reported more than 300 locations in France. SecurityWeek said most damage was in France but that retailers in Belgium, Germany, the Netherlands, Poland, Portugal and Spain were also affected.

Dominique Schelcher, chief executive of Coopérative U, confirmed that several stores in the chain had been affected. ANSSI, the French national cybersecurity agency, said it was mobilised nationally to support potential victims and at European level with its counterparts. The Paris prosecutor's office told AFP it had opened an investigation. EU agriculture and food commissioner Christophe Hansen condemned the attack and named Leclerc among the victims.

Groupement Mousquetaires said the affected systems were managed by Danfoss and that filing a criminal complaint would be up to the supplier, Bloomberg reported. Danfoss has not publicly confirmed that its systems were the target, and a spokesperson did not immediately respond to a request for comment.

Exposure and an unrelated incident

Claroty said it had identified thousands of publicly accessible AK-SM 800A management interfaces and urged customers to upgrade to firmware R4.3.1, which contains the patches, warning that compromising the management interface can have significant operational consequences. The Record, citing Claroty's Team82, said more than 2,700 of the devices were exposed to the internet and that a compromised controller could switch off cooling while still reporting normal temperatures.

BleepingComputer noted a May 2025 CISA advisory on CVE-2025-41450, an authentication bypass in the Danfoss AK-SM 8xxA platform; The Record said CISA had issued an advisory covering three vulnerabilities in these controllers. No source says these flaws were used in the October attack.

Separately, Ahold Delhaize said on Monday 12 October that it had taken some systems offline after a cybersecurity incident, BleepingComputer reported. The same report said there was no evidence yet linking that incident to the supermarket attacks, and no other source connects them.

What is not known yet

  • Who carried out the attack and what they wanted.
  • How the attackers reached the controllers, and which access path or vulnerability they used.
  • Whether the flaws Claroty disclosed in the AK-SM 800A platform, or CVE-2025-41450, played any part.
  • The final number of stores and countries affected, and the total cost.
  • Whether Danfoss's own systems were involved, or only customer devices.

What to do

If you run Danfoss AK-SM refrigeration controllers

  1. Check which firmware your AK-SM 800A units run and apply Danfoss's patches for the flaws Claroty disclosed in the management platform.
  2. Take the management interface off the public internet and allow access only from trusted networks; Claroty found thousands of interfaces publicly reachable.
  3. Review controller configuration and logs for setpoint or defrost-schedule changes you did not make.
  4. Set alerts on temperature and configuration changes so an overnight change is noticed before stock is lost.

If a supplier manages your refrigeration or building controls

  1. Put in writing who is responsible for patching and monitoring the controllers, and how quickly.
  2. Agree in advance which organisation reports an attack to the authorities and who handles any criminal complaint; Groupement Mousquetaires said that would be up to Danfoss.

For everyone else

  1. Keep refrigeration and building-control networks separate from business IT and limit what those devices can reach on the internet.
  2. Check that a silent setpoint change would raise an alert to an on-call engineer, rather than being found by staff the next morning.

Update log

  • First published.

Sources

New incident reports by email

One email a week with the reports published since the last one.

Want us to look at your domain?

Give us one apex domain and we'll send back a written snapshot of what is already visible from outside. No call required.