CISA warns of unpatched Danfoss controller flaw as three older bugs join exploited list

CISA has published an advisory on a critical buffer overflow in Danfoss AK-SM 8xxA refrigeration controllers that needs no authentication and has no patch yet. In the same week, three older Danfoss controller flaws were added to the catalogue of vulnerabilities known to be exploited.

· First published

The short version

  • The unpatched flaw. CVE-2026-129713 is a stack-based buffer overflow in an unauthenticated web handler of Danfoss AK-SM 8xxA controllers running version 5.4.0 or earlier. CISA scores it 9.8 and says crafted HTTP/S requests can corrupt memory and restart the webserver, with code execution possible in theory.
  • Older flaws listed. CISA added three Danfoss AK-SM 800A flaws to its Known Exploited Vulnerabilities catalogue: CVE-2023-25914, CVE-2023-25915 and CVE-2025-41450. They cover path traversal, command injection and an authentication weakness that exposes internal addresses, usernames and store names.
  • Exploitation. CISA says it has no report of public exploitation of CVE-2026-129713. Danfoss has not said the three older flaws were exploited, though The Hacker News says it is likely they were used in attacks on European supermarket chains.
  • Mitigation. Until version 5.5.x arrives, administrators are advised to configure units to Strict Mode, use strong passwords, and allow remote access only through a secure VPN or protected network. CISA advises keeping controllers off the internet and behind firewalls, separated from business networks.

Timeline

DateEvent
OctoberAttacks hit retail sites in France; France attributes them to Shahid Kaveh, also known as Cyber Aveng3rs, according to The Hacker News.
24 NovCISA publishes an advisory on CVE-2026-129713 in Danfoss AK-SM 8xxA controllers, with a fix not yet available.
NovemberCISA adds three older Danfoss AK-SM 800A flaws, alongside vulnerabilities in other vendors' products, to its Known Exploited Vulnerabilities catalogue.

The unpatched flaw

CISA published the advisory on 24 November. CVE-2026-129713 is a stack-based buffer overflow — a memory corruption bug that occurs when more data is written into a fixed-size buffer than it holds — in an unauthenticated CGI handler, the part of the controller's web server that processes requests. Specially crafted HTTP/S POST requests cause memory corruption and a webserver restart, and could in theory let an attacker run code with webserver privileges. CISA gives it a CVSS score of 9.8.

Versions 5.4.0 and earlier are affected. Danfoss expects to fix the flaw in version 5.5.x and says it will remove the ability for users to disable Strict Mode in future releases. Carlo Meijer of Midnight Blue reported the flaw to CISA. CISA states that no public exploitation specifically targeting this vulnerability has been reported to it.

Three older flaws now listed as exploited

The Hacker News reports that CISA added 10 flaws to its Known Exploited Vulnerabilities (KEV) catalogue. Three concern Danfoss AK-SM 800A controllers: CVE-2023-25914, a path traversal flaw scored 8.8; CVE-2023-25915, an input validation flaw scored 9.9 that allows remote command execution; and CVE-2025-41450, an authentication flaw scored 8.5 that can produce a web report exposing internal IP addresses, usernames and store names.

Danfoss has not said these flaws were exploited, according to The Hacker News, which adds that it is likely they were used in high-impact attacks on supermarket chains in Europe. The article says France has attributed October 2026 attacks on its retail sites to Shahid Kaveh, also known as Cyber Aveng3rs and Cyber Isnaad Front, an Iranian unit affiliated with the Islamic Revolutionary Guard Corps (IRGC). No source states that the Danfoss flaws were used in those attacks.

Exposure and the wider batch

CISA lists the controllers under the commercial facilities sector and says they are deployed worldwide; Danfoss is headquartered in Denmark. The agency recommends minimising network exposure for control-system devices, placing them behind firewalls and isolating them from business networks, and using a VPN where remote access is needed.

The same KEV batch included five Mitel MiCollab flaws, an authentication bypass in Vates Xen Orchestra and a command injection in Juniper Session Smart Conductor and Session Smart Router. No source connects those products to the Danfoss flaws.

What is not known yet

  • Who is exploiting the three Danfoss flaws now in the KEV catalogue, and whether the October attacks on French retailers used them.
  • How many controllers or organisations are affected by any of the four flaws.
  • Whether an attacker has taken data or disrupted refrigeration using these flaws.
  • When Danfoss will release version 5.5.x.
  • Whether CVE-2026-129713 has been exploited without CISA's knowledge.

What to do

If you run Danfoss AK-SM 8xxA controllers

  1. Turn on Strict Mode; Danfoss says it will remove the option to disable it in future releases.
  2. Allow remote access only through a VPN or another protected network, never directly from the internet.
  3. Use strong passwords on the units.
  4. Plan to apply version 5.5.x when it ships, and check Danfoss's advisory for fixes to the three older flaws.

If you manage control-system networks

  1. Keep controllers behind a firewall and separate them from business networks.
  2. Reduce the number of control-system devices that can be reached from the internet.
  3. Keep VPN software current, since a VPN is only as secure as the devices connected to it.

For everyone else

  1. Ask whoever operates your refrigeration or building equipment whether those controllers are reachable from the internet, and require the protections above where they are.

Update log

  • First published.

Sources

New incident reports by email

One email a week with the reports published since the last one.

We email you about this topic only; unsubscribe any time. See our Privacy Policy.

Want us to look at your domain?

Give us one apex domain and we'll send back a written snapshot of what is already visible from outside. No call required.